Parameter List
Parameter list (by parameter number)
103
Pr.
List
5
─
243
T041
Terminal 1 added compensation
amount (terminal 4)
0 to 100%
0.1%
75%
─
244
H100
Cooling fan operation selection
0, 1, 101 to 105
1
1
Sl
ip
compe
n
sa
ti
on
245
G203
Rated slip
0 to 50%, 9999
0.01%
9999
246
G204
Slip compensation time constant
0.01 to 10 s
0.01 s
0.5 s
247
G205
Constant-power range slip
compensation selection
0, 9999
1
9999
─
248
A006
Self power management selection
0 to 2
1
0
─
249
H101
Earth (ground) fault detection at
start
0, 1
1
0
─
250
G106
Stop selection
0 to 100 s,
1000 to 1100 s, 8888,
9999
0.1 s
9999
─
251
H200
Output phase loss protection
selection
0, 1
1
1
Freq
uen
cy
compe
n
sa
ti
on
fun
c
tio
n
252
T050
Override bias
0 to 200%
0.1%
50%
253
T051
Override gain
0 to 200%
0.1%
150%
─
254
A007
Main circuit power OFF waiting time
1 to 3600 s, 9999
1 s
600 s
Life check
255
E700
Life alarm status display
(0 to 15)
1
0
256
E701
Inrush current limit circuit life
display
(0 to 100%)
1%
100%
257
E702
Control circuit capacitor life display
(0 to 100%)
1%
100%
258
E703
Main circuit capacitor life display
(0 to 100%)
1%
100%
259
E704
Main circuit capacitor life
measuring
0, 1
1
0
─
260
E602
PWM frequency automatic
switchover
0, 1
1
1
Power fa
il
ure
stop
261
A730
Power failure stop selection
0 to 2, 11, 12, 21, 22
1
0
262
A731
Subtracted frequency at
deceleration start
0 to 20 Hz
0.01 Hz
3 Hz
263
A732
Subtraction starting frequency
0 to 590 Hz, 9999
0.01 Hz
60 Hz
264
A733
Power-failure deceleration time 1
0 to 3600 s
0.1 s
5 s
265
A734
Power-failure deceleration time 2
0 to 3600 s, 9999
0.1 s
9999
266
A735
Power failure deceleration time
switchover frequency
0 to 590 Hz
0.01 Hz
60 Hz
─
267
T001
Terminal 4 input selection
0 to 2
1
0
─
268
M022
Monitor decimal digits selection
0, 1, 9999
1
9999
─
269
E023
Parameter for manufacturer setting. Do not set.
─
270
A200
Stop-on contact/load torque high-
speed frequency control selection
0 to 3, 11, 13
1
0
L
o
ad
t
o
rque
hi
gh
s
p
ee
d
frequency control
271
A201
High-speed setting maximum
current
0 to 400%
0.1%
50%
272
A202
Middle-speed setting minimum
current
0 to 400%
0.1%
100%
273
A203
Current averaging range
0 to 590 Hz, 9999
0.01 Hz
9999
274
A204
Current averaging filter time
constant
1 to 4000
1
16
St
o
p
-o
n
contac
t
cont
ro
l
275
A205
Stop-on contact excitation current
low-speed multiplying factor
0 to 300%, 9999
0.1%
9999
276
A206
PWM carrier frequency at stop-on
contact
0 to 9, 9999
1
9999
0 to 4, 9999
Functio
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
settin
g