(M) Monitor display and monitor output signal
379
5
GROUP
M
5.11.7
Output frequency detection
Output up-to-frequency sensitivity (SU signal, Pr.41)
The inverter output frequency is detected and output as output signals.
Pr.
Name
Initial value Setting range
Description
41
M441
Up-to-frequency
sensitivity
10%
0 to 100%
Set the level where the SU signal turns ON.
42
M442
Output frequency
detection
6 Hz
0 to 590 Hz
Set the frequency where the FU (FB) signal turns ON.
43
M443
Output frequency
detection for reverse
rotation
9999
0 to 590 Hz
Set the frequency where the FU (FB) signal turns ON in
reverse rotation.
9999
Same as the
Pr.42
setting.
50
M444
Second output
frequency detection
30 Hz
0 to 590 Hz
Set the frequency where the FU2 (FB2) signal turns ON.
116
M445
Third output frequency
detection
60 Hz
0 to 590 Hz
Set the frequency where the FU3 (FB3) signal turns ON.
865
M446
Low speed detection
1.5 Hz
0 to 590 Hz
Set the frequency where the LS signal turns ON.
870
M400
Speed detection
hysteresis
0 Hz
0 to 5 Hz
Set the hysteresis width for the detected frequency.
• Up to frequency (SU) is output when the output frequency reaches the set
frequency.
• The
Pr.41
value can be adjusted within the range ±1% to ±100%
considering the set frequency as 100%.
• This parameter can be used to check that the set frequency has been
reached, and provide signals such as the operation start signal for related
equipment.
Output frequency
(Hz)
ON
Set frequency
Adjustment
range
Pr.41
SU
Time
OFF
OFF