
(G) Control parameters
622
Droop control
• Droop control is enabled for Advanced magnetic flux vector control, Real sensorless vector control, vector control, and PM
sensorless vector control.
• Output frequency will change depending on the size of the current for torque with the droop control.
Set % of the droop amount of rated torque with rated frequency (motor speed in case of
Pr.288
= "10, 11") as a reference
for the droop gain.
• Upper limit of the droop compensation frequency is smaller frequency between 400 Hz and
Pr.1 Maximum frequency
.
• During PM sensorless vector control, the lowest frequency among 400 Hz,
Pr.1
, and maximum motor frequency becomes
the upper limit droop compensation frequency.
• The droop compensation frequency is calculated as follows.
NOTE
• Setting of the droop gains should be approximately the rated slip of the motor.
• The speed loop integration can be disabled at the emergency stop using
Pr.1349 Emergency stop operation selection
.
(Refer to
Limiting the frequency after the droop compensation (0 limit)
• By setting
Pr.288
at the time of Real sensorless vector control, vector control, or PM sensorless control, the negative
frequency command when the frequency after droop compensation can be limited.
During Advanced magnetic flux vector control, the action same as the "0" setting will be performed.
Rated slip
=
Synchronized speed at the time of base frequency - rated rotation speed
100 [%]
Synchronized speed at the time of base frequency
Pr.288
setting
Operation
When the output frequency after droop
compensation is negative
Droop compensation
reference
0 (initial value)
No droop control during
acceleration/deceleration
Limited at 0 Hz
(limited at 0.5 Hz under Advanced magnetic flux vector
control)
Rated motor frequency
(
Pr.84
setting)
10
Motor speed
20
Per-unit speed control
reference frequency
(
Pr.1121
setting)
Continuous droop control during
operation
Rated motor frequency
(
Pr.84
setting)
Motor speed
21
Per-unit speed control
reference frequency
(
Pr.1121
setting)
Continuous droop control during
operation
Not limited (but reversed) under Vector control or PM
sensorless vector control
Limited at 0 Hz under Real sensorless vector control
Rated motor frequency
(
Pr.84
setting)
22
Per-unit speed control
reference frequency
(
Pr.1121
setting)
Droop compensation
frequency
Torque
100%
Droop
gain
-100%
Frequency
0
Droop compensation
reference
Current for torque after filtering
Rated torque current
× K ×
Droop compensation frequency =
Droop compensation reference × Droop gain
100
When the output frequency is equal to or lower than the rated frequency set in
Pr.84
: K
=
1
When the output frequency is higher than the rated frequency set in
Pr.84
: K =
Output frequency
Rated frequency (
Pr.84
)
Summary of Contents for 800 Series
Page 11: ...MEMO 10 ...
Page 17: ...MEMO 16 ...
Page 95: ...MEMO 94 ...
Page 671: ...MEMO 670 ...
Page 681: ...MEMO 680 ...