(N) Operation via communication and its settings
578
Error response
• An error response is returned if the query message received from the master contains an illegal function, address or data.
No response is returned for parity, CRC, overrun, framing, and Busy errors.
NOTE
• No response is also returned in the case of broadcast communication.
• Error response (Response message)
• Error code list
An error does not occur in the following cases:
• Function code H03 (read data of holding register)
When there are 1 or more number of reads (No. of Points) and there is 1 or more holding register from where data can be read
• Function code H10 (write data to multiple holding registers)
When there are 1 or more number of writes (No. of Registers) and there is 1 or more holding registers to which data can be written.
In other words, when function code H03 or H10 is used and multiple holding registers are accessed, an error will not occur even if a non-
existent holding register or holding register that cannot be read or written is accessed.
NOTE
• An error will occur if all accesses holding registers do not exist. The data read value of non-existent holding registers is 0, and
data is invalid when written to non-existent holding registers.
• Error detection of message data
The following errors are detected in message data from the master. The inverter is not tripped even if an error is detected.
Error check items
NOTE
• The LF signal can be assigned to an output terminal by setting
Pr.190 to Pr.196 (Output terminal function selection)
.
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
a. Slave
Address
b. Function
c. Exception
Code
CRC Check
(8 bits)
H80 + Function
(8 bits)
(8 bits)
L
(8 bits)
H
(8 bits)
Message
Description
a
Slave Address
Set the address received from the master.
b
Function
The function code requested by the H80 is set.
c
Exception Code
The codes in the following table are set.
Code
Error Item
Error description
01
ILLEGAL FUNCTION
The query message from the master is set with a function code that cannot be
handled by the slave.
02
ILLEGAL DATA ADDRESS
The query message from the master is set with a register address that cannot
be handled by the inverter.
(No parameter, parameter cannot be read, parameter cannot be written)
03
ILLEGAL DATA VALUE
The query message from the master is set with data that cannot be handled by
the inverter.
(Out of parameter write range, a mode is specified, other error)
Error item
Error description
Inverter operation
Parity error
The data received by the inverter is different from the
specified parity (
Pr.334
setting).
When this error occurs,
Pr.343
is
incremented by one.
When this error occurs, the LF signal is
output.
Framing error
The data received by the inverter is different from the
stop bit length (
Pr.333/Pr.334
)
setting.
Overrun error
The next data has been sent by the master before
the inverter completes receiving the preceding data.
Message frame error
The data length of the message frame is checked,
and an error is generated if the received data length
is less than 4 bytes.
CRC check error
An error is generated if the data in the message
frame does not match the calculation result.