(A) Application parameters
464
Setting the stop-on-contact control
• Make sure that the inverter is in External or Network operation mode. (Refer to
.)
• Select either Real sensorless vector control (speed control) or Advanced magnetic flux vector control.
• Set "1, 3, 11 or 13" in
Pr.270 Stop-on contact/load torque high-speed frequency control selection
.
• Set the output frequency for stop-on-contact control in
Pr.6 Multi-speed setting (low speed)
.
Set the frequency as low as possible (about 2 Hz). If a frequency higher than 30 Hz is set, it operates with 30 Hz.
• When both the RT and RL signals are switched ON, the inverter enters the stop-on-contact control, and operation is
performed at the frequency set in
Pr.6
independently of the preceding speed.
•
Setting Pr.270
= "11 or 13" disables stall prevention stop (E.OLT) during stop-on-contact control (with both RL and RT
signals ON).
NOTE
• By increasing the
Pr.275
setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OC[]) may occur
or the machine may oscillate in stop-on-contact status.
• The stop-on-contact function is different from the servo-lock function, and if used to stop or hold a load for an extended
period, this function can cause the motor to overheat.
After a stop, immediately switch to a mechanical brake to hold the load.
• Under the following operating conditions, the stop-on-contact function is invalid:
PU operation
(Pr.79)
, JOG operation (JOG signal), PU + External operation
(Pr.79)
, PID control function operation
(Pr.128)
,
Remote setting function operation
(Pr.59)
,
Automatic acceleration/deceleration
(Pr.292)
, Start time tuning, Orientation control
function operation
• When performing stop-on-contact control during encoder feedback control, encoder feedback control is invalid due to a
transition to the stop-on-contact control mode.
Function switching of stop-on-contact control selection
When RL and RT are ON,
Pr.49 Second stall prevention operation frequency
is invalid.
Main functions
Normal operation
(either RL or RT is OFF or both are OFF)
Stop-on-contact control
(both RL and RT are ON)
Real sensorless
vector control
Advanced
magnetic flux
vector control
Real sensorless
vector control
Advanced
magnetic flux
vector control
Output frequency
Multi-speed, 0 to 5 V, 0 to 10 V 4 to 20 mA, etc.
Pr.6
setting
Stall prevention operation
level
—
Pr.22
setting
—
The smaller value set in
either
Pr.22
or
Pr.48
Torque limit level
Pr.22
setting
—
Pr.22
setting
—
Excitation current low-
speed scaling factor
—
The current is compensated by
Pr.275
(50 to
300%) setting from normal operation.
Carrier frequency
Pr.72
setting
When output frequency is 3 Hz or lower,
Pr.276
setting (
Pr.72
when
Pr.276
= "9999")
Fast-response current
limit
—
Enabled
—
Disabled