(C) Motor constant parameters
435
5
GROUP
C
Tuning the second applied motor
• When one inverter switches the operation between two different motors, set the second motor in
Pr.450 Second applied
motor
. (Refer to
.) In the initial setting, no second motor is applied.
• Turning ON the RT signal will enable the parameter settings for the second motor as shown below.
NOTE
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of
Pr.178 to Pr.189 (Input terminal function
selection)
to assign the RT signal to another terminal.
• Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
???????
Parameters referred to
Pr.1 Maximum frequency
Pr.9 Electronic thermal O/L relay
Pr.31 to Pr.36 Frequency jump
Pr.71 Applied motor
Pr.156 Stall prevention operation selection
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.800 Control method selection
Function
RT signal ON (second motor)
RT signal OFF (first motor)
Motor capacity
Pr.453
Pr.80
Number of motor poles
Pr.454
Pr.81
Motor excitation current
Pr.455
Pr.82
Rated motor voltage
Pr.456
Pr.83
Rated motor frequency
Pr.457
Pr.84
Motor constant (R1)
Pr.458
Pr.90
Motor constant (R2)
Pr.459
Pr.91
Motor constant (L1)/d-axis
inductance (Ld)
Pr.460
Pr.92
Motor constant (L2)/q-axis
inductance (Lq)
Pr.461
Pr.93
Motor constant (X)
Pr.462
Pr.94
Auto tuning setting/status
Pr.463
Pr.96
Frequency search gain
Pr.560
Pr.298
Summary of Contents for 800 Series
Page 11: ...MEMO 10 ...
Page 17: ...MEMO 16 ...
Page 95: ...MEMO 94 ...
Page 671: ...MEMO 670 ...
Page 681: ...MEMO 680 ...