
Position control under vector control
215
5
Example 3 of positioning operation by point tables (variable speed
operation)
• The maximum frequency can be changed during positioning operation. Use as many point tables as the number of
maximum speeds to be set.
• The figure below shows an operation example when the following settings are made for point tables.
• Set "0" as the dwell time to perform variable speed operation.
Return to home position during point table positioning
• Home position return is performed to match the command coordinates with the machine coordinates.
• The returned home position can be set as point 0, and positioning operation is available using this.
• Home position return procedure
1) Set parameters related to home position return.
• Set the home position return method (
Pr.1282
).
• Set the speed for home position return operation (
Pr.1283
).
• Set the creep speed for home position return operation (
Pr.1284
).
• Set the home position return shift amount if necessary (
Pr.1286
10000 +
Pr.1285
).
• Set the post proximity dog travel distance if necessary (
Pr.1288
10000 +
Pr.1287
).
2) Turn OFF all point table selections.
• Turn OFF all RH, RM, RL and REX signals.
3) Turn ON the Pre-excitation/servo ON (LX) signal.
4) Turn ON the start signal (STF or STR).
• Home position return is performed according to the settings.
NOTE
• The setting values of the point table 1 are used as acceleration/deceleration time.
• After turning ON the start signal, only the setting values of
Pr.1283 Home position return speed or Pr.1284 Home position
return creep speed
can be changed.
• Perform home position return at the motor switchover.
Point
table
Target position
Maximum
speed (Hz)
Acceleration
time (s)
Deceleration
time (s)
Dwell time
(ms)
Auxiliary function
Upper
Lower
1
5
0
30
1
1
0
1 (absolute position, continuous)
2
3
0
20
Invalid
Invalid
0
11 (incremental position, individual)
3
10
0
10
Invalid
Invalid
0
1 (absolute position, continuous)
4
6
0
5
Invalid
Invalid
0
10 (incremental position, individual)
0
30 Hz
(
Pr.4
)
Time
Position command
speed
STF
Acceleration time (1 s)
of point table 1
20 Hz
(
Pr.5
)
10 Hz
(
Pr.6
)
5 Hz
(
Pr.24
)
Deceleration time (1 s)
of point table 1
Position feed length
50000
50000
80000
100000
160000
0
30000
20000
60000
RH
RM
RL
Servo ON
(LX)
ON
ON
ON
Summary of Contents for 800 Series
Page 11: ...MEMO 10 ...
Page 17: ...MEMO 16 ...
Page 95: ...MEMO 94 ...
Page 671: ...MEMO 670 ...
Page 681: ...MEMO 680 ...