(H) Protective function parameter
341
5
GROUP
H
• Setting "8888" in
Pr.1481 to Pr.1485
enables fine adjustment of load characteristics. When setting
Pr.1481 to Pr.1485
=
"8888" during operation, the load status at that point is set in the parameter. (Only when the set frequency is within ±2 Hz of
the frequency of the measurement point, and SU signal is in the ON state.)
NOTE
• Even if the load measurement is not properly completed, the load characteristics fault is detected based on the load
characteristics found by the already-completed portion of the measurement.
• During the load characteristics measurement, the load characteristics fault detection is not performed.
• During the load characteristics measurement, linear acceleration/deceleration is performed even if the S-pattern acceleration/
deceleration is set.
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Load fault detection setting (Pr.1488 to Pr.1491)
• When the load is deviated from the detection width set in
Pr.1488 Upper limit warning detection width
, the Upper limit
warning detection (LUP) signal is output. When the load is deviated from the detection width set in
Pr.1489 Lower limit
warning detection width
, the Lower limit warning detection (LDN) signal is output. At the same time, the Load fault
warning (LDF) appears on the operation panel.
• For the LUP signal, assign the function by setting "211 (positive logic)" or "311 (negative logic)" in any of
Pr.190 to Pr.196
(Output terminal function selection)
. For the LDN signal, assign the function by setting "212 (positive logic)" or "312
(negative logic)" in any of
Pr.190 to Pr.196 (Output terminal function selection)
.
• When the load is deviated from the detection width set in
Pr.1490 Upper limit fault detection width
, the protective
function (E.LUP) is activated and the inverter output is shut off. When the load is deviated from the detection width set in
Pr.1491 Lower limit fault detection width
, the protective function (E.LDN) is activated and the inverter output is shut off.
f2
f1(
Pr.1487
)
f3
f4
f5(
Pr.1486
)
Frequency(Hz)
Time
Pr.1492
Load reference
1 recorded
Load reference 2 recorded
Load reference 3 recorded
Load reference 4 recorded
Load reference 5 recorded
STF
=
ON
Pr.1480
=1
Measurement start
Example of starting measurement from the stop state
SU signal
Y213
1
2
3
4
5
0
Read value of
Pr.1480
Pr.41
Pr.41
Pr.41
Pr.41
Pr.41
Pr.1492
Pr.1492
Pr.1492
Pr.1492
STF
ON
ON
ON
ON
ON
ON
ON
ON
Operation at the
set frequency