489
5
GROUP
A
609
A624
PID set point/deviation
input selection
2
1
Input of set point, deviation value from terminal 1
2
Input of set point, deviation value from terminal 2
3
Input of set point, deviation value from terminal 4
4
Input of set point, deviation value via communication
5
Input of set point, deviation value by PLC function
610
A625
PID measured value
input selection
3
1
Input of measured value from terminal 1
2
Input of measured value from terminal 2
3
Input of measured value from terminal 4
4
Input of measured value via communication
5
Input of measured value by sequence function
1015
A607
Integral stop selection
at limited frequency
0
0
Integral stopped at the limit, manipulation range of ±100%,
integral cleared during output interruption
1
Integral continued at the limit, manipulation range of ±100%,
integral cleared during output interruption
2
Integral stopped at the limit, manipulation range of 0 to
100%, integral cleared during output interruption
10
Integral stopped at the limit, manipulation range of ±100%,
integral stopped during output interruption
11
Integral continued at the limit, manipulation range of ±100%,
integral stopped during output interruption
12
Integral stopped at the limit, manipulation range of 0 to
100%, integral stopped during output interruption
753
A650
Second PID action
selection
0
0, 10, 11, 20, 21,
50, 51, 60, 61, 70,
71, 80, 81, 90, 91,
100, 101, 1000,
1001, 1010, 1011,
2000, 2001, 2010,
2011
Refer to
Pr.128
.
Set the second PID control.
For how to enable the second PID
control, refer to
.
754
A652
Second PID control
automatic switchover
frequency
9999
0 to 600 Hz, 9999
Refer to
Pr.127
.
755
A651
Second PID action set
point
9999
0 to 100%, 9999
Refer to
Pr.133
.
756
A653
Second PID
proportional band
100
0.1 to 1000%,
9999
Refer to
Pr.129
.
757
A654
Second PID integral
time
1 s
0.1 to 3600 s,
9999
Refer to
Pr.130
.
758
A655
Second PID differential
time
9999
0.01 to 10 s, 9999 Refer to
Pr.134
.
1140
A664
Second PID set point/
deviation input
selection
2
1 to 5
Refer to
Pr.609
.
1141
A665
Second PID measured
value input selection
3
1 to 5
Refer to
Pr.610
.
1143
A641
Second PID upper limit
9999
0 to 100%, 9999
Refer to
Pr.131
.
1144
A642
Second PID lower limit
9999
0 to 100%, 9999
Refer to
Pr.132
.
1145
A643
Second PID deviation
limit
9999
0 to 100%, 9999
Refer to
Pr.553
.
(Y205 signal is
output.)
1146
A644
Second PID signal
operation selection
0
0 to 3, 10 to 13
Refer to
Pr.554
.
1147
A661
Second output
interruption detection
time
1 s
0 to 3600 s, 9999
Refer to
Pr.575
.
1148
A662
Second output
interruption detection
level
0 Hz
0 to 600 Hz
Refer to
Pr.576
.
1149
A663
Second output
interruption cancel level
1000%
900 to 1100%
Refer to
Pr.577
.
Pr.
Name
Initial
value
Setting range
Description