(D) Operation command and frequency command
297
5
GROUP
D
PU operation interlock (Pr.79
=
"7")
• The operation mode can be forcibly switched to the External operation mode by turning OFF of the PU operation interlock
(X12) signal. This function prevents the operation mode from being accidentally unswitched from the PU operation mode. If
the operation mode left unswitched from the PU operation mode, the inverter does not reply to the commands sent through
external commands.
• To input the X12 signal, set "12" in any of
Pr.178 to Pr.189 (Input terminal function selection)
to assign the function to a
terminal. (For details on
Pr.178 to Pr.189
, refer to
.)
• Set
Pr.79
="7" (PU operation interlock).
• If the X12 signal is not assigned, the function of the MRS signal is switched to PU operation internal signal from MRS
(output stop).
Depends on the
Pr.77 Parameter write selection
setting and the writing conditions of each parameter. (Refer to
.
)
• Functions/operations by X12 (MRS) signal ON/OFF
The mode is switched to the External operation mode regardless of the ON/OFF state of the start signals (STF, STR). Thus, the motor runs
under the External operation mode when the X12 (MRS) signal turns OFF with either of STF or STR in an ON state.
When a fault occurs, the inverter can be reset by pressing
on the operation panel.
NOTE
• The operation mode cannot switched to the PU operation mode with the start signal (STF, STR) in an ON state even if the
X12 (MRS) signal is ON.
• If the MRS signal is ON and
Pr.79
is written to a value other than "7" when the MRS signal is used as the PU interlock signal
during PU operation mode, the MRS signal will act as a regular MRS function (output stop). Also, when
Pr.79
="7", the MRS
signal becomes the PU interlock signal.
• The logic of the signal follows the
Pr.17 MRS input selection
setting also when the MRS signal is used as the PU operation
interlock signal. When
Pr.17
="2", ON and OFF in the above explanation are reversed.
• Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
X12 (MRS)
signal
Function/Operation
Operation mode
Parameter writing
ON
Switching of the operation mode (External, PU, and
NET) is enabled.
Output is stopped during External operation.
Parameter writing enabled
OFF
Operation mode is forcefully changed to the External
operation mode.
External operation is enabled.
Switching to the PU or NET operation mode from the
External operation mode is disabled.
Writing of parameters other than
Pr.79
is disabled.
Operating status
X12 (MRS) signal
Operation
mode
Operating status
Switching to
PU or NET
operation mode
Operation
mode
Status
PU/NET
during a
stop
ON
→
OFF
If frequency and start commands are input from
external source, the inverter runs by those
commands.
Not available
Running
ON
→
OFF
Not available
External
during a
stop
OFF
→
ON
during a stop
Available
ON
→
OFF
Not available
Running
OFF
→
ON
Running
→
Output shutoff
Not available
ON
→
OFF
Output shutoff
→
Running
Not available