495
5
GROUP
A
PID automatic switchover control (Pr.127)
• The system can be started up more quickly by starting up without PID control activated.
• When
Pr.127 PID control automatic switchover frequency
is set, the startup is made without PID control until the output
frequency reaches the
Pr.127
setting. Once the PID control starts, the PID control is continued even if the output frequency
drops to
Pr.127
setting or lower.
Selection of action at a communication error and sleep function stop
selection (FUP signal, FDN signal, Y48 signal, Pr.554)
• Using
Pr.554 PID signal operation selection
, set the action when the measured value input exceeds the upper limit
(Pr.131 PID upper limit)
or lower limit
(Pr.132 PID lower limit)
, or when the deviation input exceeds the permissible value
(Pr.553 PID deviation limit)
.
• Choose whether to output the signals (FUP, FDN, Y48) only or to activate the protective function to output the inverter
shutoff.
• The stop action when the inverter output is shut off by the SLEEP function can be selected.
Pr.554 setting
Inverter operation
At FUP signal, FDN signal output
At Y48 signal output
At SLEEP operation start
0 (Initial value)
Signal output only
Signal output only
Coasts to stop
1
Signal output shutoff (E.PID)
2
Signal output only
Signal output shutoff
(E.PID)
3
Signal output shutoff (E.PID)
10
Signal output only
Signal output only
Deceleration stop
11
Signal output shutoff (E.PID)
12
Signal output only
Signal output shutoff
(E.PID)
13
Signal output shutoff (E.PID)
When each of
Pr.131, Pr.132 and Pr.553
corresponding to each of the FUP, FDN and Y48 signals is set to "9999" (function not
activated), signal output and protective function are disabled.
Output frequency
Pr.127
STF
Time
PID
PID control
Without PID
control