(E) Environment setting parameters
245
5
GROUP
E
When any of "100 to 103, 114 to 117, 1100 to 1103, or 1114 to 1117" is set in
Pr.75
, the reset limit function is enabled. (The reset limit function is
available for the FR-A860-01440 or higher.)
Reset selection (P.E100)
• When
P.E100
="1" or
Pr.75
="1, 3, 15, 17, 100, 103, 115, or 117" is set, reset (reset command via the RES signal or
communication) input is enabled only when the protective function is activated.
• While
P.E100
= "2" or
Pr.75
= "1000, 1002, 1014, 1016, 1100, 1102, 1114, or 1116", the reset command input is enabled
(using the RES signal or through communication) only when the start signal is OFF.
• While
P.E100
= "3" or
Pr.75
= "1001, 1003, 1015, 1017, 1101, 1103, 1115, or 1117", the reset command input is enabled
(using the RES signal or through communication) only when the protective function is activated with the start signal OFF.
NOTE
• When the RES signal is input during operation, the motor coasts since the inverter being reset shuts off the output. Also, the
cumulative values of electronic thermal O/L relay and regenerative brake duty are cleared.
• When "reset input always enabled" is selected, the reset key on the PU is enabled only when the protective function is
activated.
• The following table shows applicable start commands. (When both the STF and STR signals are ON, the start signal status is
OFF.
)
14 (initial
value), 114
Reset command input always enabled.
Operation continues even when
PU is disconnected.
The inverter decelerates to a
stop when
is pressed in
any operation mode of the PU,
External, or Network.
15, 115
Reset command input enabled only when the
protective function activated.
1014, 1114
Reset input enabled only when the start signal is
OFF.
1015, 1115
Reset input enabled only when the protective
function is activated and the start signal is OFF.
16, 116
Reset command input always enabled.
Inverter output shut off when PU
is disconnected.
17, 117
Reset command input enabled only when the
protective function activated.
1016, 1116
Reset input enabled only when the start signal is
OFF.
1017, 1117
Reset input enabled only when the protective
function is activated and the start signal is OFF.
Start signal input interface
Applicable start signal
External terminal
X13, X22, LX, X28, JOGF, JOGR, STF, or STR
PU
Forward/reverse rotation command given by
pressing the FWD/REV key
Communication
X13, X22, LX, X28, STF, or STR
Pr.75
setting
Reset selection
Disconnected PU
detection
PU stop selection