108
Appendix B: Using the Configurator
Some columns containing advanced or internal information are normally hidden. They are
listed as Visible / No in the following table. Other columns are conditionally visible.
Flag Columns
There are up to three Flag columns (F1, F2 and F3) for flags of various types.
NS - Non Silenceable - used on inputs and supervised Outputs
GA - 2nd Stage Alarm - in two stage system
ND - No Display - indicates that activation of this zone is not to be displayed in the queue. A
similar flag applies to indvidual devices. By default, devices do not have the flag set and zones
do.
LED Annunciator Summary
An FX-2000 job's Network Node can have multiple LED Annunciators, but they all share the
same programming. There is therefore a maximum of one such item per Network Node in the
tree view.
This list view is displayed in the top, right pane of the user interface when a LED Annunciator
item is selected in the job tree. It shows the addresses and tags of each instance.
Name
Visible
Description
Addr
No
A sequentially assigned zone address. Allocated for consistency
with other loop types.
Lp
No
Loop Number. Not meaningful for zones
Lp Addr
No
A sequentially assigned zone number or address.
Ckt No
No
An internal, sequentially assigned number.
Ckt No CPU
No
An internal, sequentially assigned number: the CKT_NO within
the CKT_IPT_ZONES.
Device
Yes
Always Input Zone.
Type
Yes
The process Type of the Zone. Can be edited (combo box).
Code
On Coded
Systems
Inputs on Coded Systems only. Devices or circuits may
optionally be associated with a code to be sounded on the signal
circuits to indicate where the alarm has occurred. The code
consists of 1 to 4 digits, each digit consisting of 1-15 pulses on
the signals. Each coded circuit can be configured to sound the
complete code 1 - 15 times after which the signals will either go
silent or revert to the programmed GA rate. Embedded zeros
and zero repetition counts are illegal. (1-0-2(3) is illegal, as is
4(0)).
Sens No
No
No applicable to input zones.
Sens B No
No
No applicable to input zones.
Tag1 and 2
Yes
The text of the tag, in two 20 character fields, representing the
two lines displayed on the front panel when an alarm occurs, etc.