111
Appendix B: Using the Configurator
Flag Columns
There are up to three Flag columns (F1, F2 and F3) for flags of various types.
•
AR - Auxiliary Reset required - used on Relay
•
BU - Back Up amplifier - used on audio controller. Designates the amplifier as the back
up. It must be of sufficient power to substitute any of the other configured amplifiers. The
back up amplifier can only accept correlations to status LEDs, trouble LEDs and UDACT
groups.
•
ER - Enable Required - used on switches for security (code or key)
•
GA - 2nd Stage Alarm - in two stage system or to return the supervised signal to EVAC
rate after code is completed in coded System
•
NB - Non Bypassable used on relays
•
NC - Not coded - used on supervised outputs i.e. Strobe to keep the strobe operating
until Reset (even after Code has ended)
•
ND - No Display - indicates that activation of this input device is not to be displayed in
the queue. A similar flag applies to Input Zones. By default, devices do not have the flag
set and zones do.
•
NS - Non Silenceable - used on inputs and supervised Outputs
•
SR - System Reset required - used on Switches used for Fan control
Sens B
On Addressable
Loops, if after
hours specified.
The after hours and night time alarm level 1 sensitivity of
the sensor. Displays a combo with sensitivity in
appropriate units for the device type. Required for
sensors.
Sens B Lvl 2
On Addressable
Loops, if after
hours specified.
The after hours and night time alarm level 2 sensitivity of
the sensor. Displays a combo with sensitivity in
appropriate units for the device type. Optional.
Sens B Lvl 3
On Addressable
Loops, if after
hours specified.
The after hours and night time alarm level 3 sensitivity of
the sensor. Displays a combo with sensitivity in
appropriate units for the device type. Optional if Lvl2
specified.
Tag1 and 2
Yes
The text of the tag, in two 20 character fields, representing
the two lines displayed on the front panel when an alarm
occurs, etc. The two fields are concatenated, trimmed of
trailing spaces and saved on the database.
Name
Visible
Description
Summary of Contents for Flex-Net Phase II
Page 1: ...Flex Net Phase II Application Guide LT 6045 Rev 1 October 2012 Application Guide...
Page 2: ......
Page 51: ...51 Hardware Layouts...
Page 115: ...114 Appendix B Using the Configurator...
Page 131: ......