17
BACnet
The object types that Flex-Net uses are binary input, analog input, multi-state input, life safety
point and binary output. The following table identifies which fire devices are classified under
which BACnet object types.
Each of these object types have an associated set of properties. These properties identify the
object and the state it is in. The table below lists the properties associated with each BACnet
object that are used by the Flex-Net system. Some of the properties below are static, while
others are dynamic and are used to determine the state the object is in. The dynamic
properties in the table are bolded.
Each dynamic object property uses different types of information to describe the state of the
property. The type of information reported can also vary between different object types for the
same object property. The following discussion describes the different values each dynamic
object property can have for the different object types.
BINARY INPUTS:
The
Present Value
property can be in one of two states: active or inactive.
For the
Status Flags
property a Boolean array [_,_,_,_] is displayed with each value in the
array representing the presence (1) or absence (0) of an Alarm, Fault, Override or Out of
Service respectively. For example a signal of 1,1,0,0 indicates the presence of an alarm and a
fault. Note that for Flex-Net override is never used. For the
Event State
property one of three
states is possible: normal, fault or off normal.
ANALOG INPUTS:
The
Present Value
property is represented by a raw analog value in the
form of a pulse width PW4 signal. For the
Status Flags
property a Boolean array [_,_,_,_] is
displayed with each value in the array representing the presence (1) or absence (0) of an
Object Type
Fire Device Types
Binary Input
Conventional Input, System Status, Page Select Switches, Manual
Control Switches, Miscellaneous Input Circuits
Analog Input and
Multi-State Input
Ion Detector, Photo Detector, Heat Detector, Laser Detector,
COPTIR, 4-20mA Module, Acclimate Detector
Life Safety Point
Fire Phone, Telephone Line, Generic Input
Binary Output
Amplifier, Addressable Relay, Conventional Relay, Conventional
Signal, Control
Object
Type
Binary Input
Analog Input
Multi-State
Input
Life Safety Point
Binary Output
Object
Properties
Object
Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Out of Service
Polarity
Description
Object
Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Out of Service
Units
Description
Object
Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Out of Service
Number of
States
Description
State Text
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Out of Service
Reliability
Mode
Accepted Modes
Silenced
Operation
Expected
Description
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Out of Service
Polarity
Priority Array
Relinquish
Default
Description
Active Text
Inactive Text
Summary of Contents for Flex-Net Phase II
Page 1: ...Flex Net Phase II Application Guide LT 6045 Rev 1 October 2012 Application Guide...
Page 2: ......
Page 51: ...51 Hardware Layouts...
Page 115: ...114 Appendix B Using the Configurator...
Page 131: ......