52
Appendix A: Hardware Changes
ANC-5000 Audio Network Controller
The main change to this module is the addition of an Ethernet port. Affected components are
the DIP switch, the watchdog jumper and the reset jumper. The DIP switch has been reversed
from its previous position such that switch 1 is where switch 8 used to be. The positions of the
watchdog jumper and the reset jumper have been swapped with each other. Refer to the
figure below.
JW7 JW8
IN
OUT
JW5
JW4
P13
P11
P3 For Future Use
P6 RS-485
P10 RS-485
P4 RS-232 Debug
Ethernet Port
P7
P8 H_Speed Audio
Plugs into the
QMB-5000N
Backplane
Connect
RS-485 cable
from P3 on the
main fire alarm
board to P6 IN
on this board
(daisy chain
fashion) and
from P10 OUT
to next main
fire alarm
board or to
next adder
board
Connects to TNC-5000 Telephone
Network Controller Module
+ - + - + - S + - S + - L
+ - S
+ - S
Alternate
Power
IN
G.A.
Input
IN
RS-485
PAGING BUS
MIC
PTT
IN OUT
SW1
1
8
ON
Heartbeat
FX-2000 COMM RX
FX-2000 COMM TX
QX-5000/CLASS D RX
QX-5000/CLASS D TX
QX-5000 RX
Status Page Bus IN
Status Page Bus OUT
System OK
RESET/CPU Fail
Input Level
Jumper s JW7 and
JW8 normally shorted
to be removed for
microphone input
LEDs for
Information
P13 Ethernet
Port for Future Use
JW4 Jumper Factory
Use Only, Leave Open
JW5 Jumper Watch-
dog , Leave Shorted
NOTE: All connectors not shown on this drawing are for factory use only.
P4 For Factory
Use Only
High Speed Audio
Bus Connects to
Main Board P16
G.A. Input and
RS-485 are for
Future Use
Summary of Contents for Flex-Net Phase II
Page 1: ...Flex Net Phase II Application Guide LT 6045 Rev 1 October 2012 Application Guide...
Page 2: ......
Page 51: ...51 Hardware Layouts...
Page 115: ...114 Appendix B Using the Configurator...