105
Appendix B: Using the Configurator
•
Aux disconnect
•
If enabled, the dialer will block the alarm and supervisory events from being
reported after the auxiliary disconnect button is pressed.
Display Adder
This list view appears in the top, right pane of the user interface when a display adder is
selected in the Job Tree. The list displays items (LEDs and Switches) of all the frames on the
selected Display Adder.
Name
Visible
Description
Idx
Yes
Index - the zero based position of the item on the adder.
Node
No
The Node Number of the Annunciator to which the adder is
attached.
CPU
No
The CPU Number of the Annunciator to which the adder is
attached.
Unnamed
Yes
Linked Item - contains an asterisk if the item shares the same
LedGrp with other items. This means that correlations to one
such item are added to all linked items. Linked Items can be
created when Paste Special is used. The linked items can be
viewed with the Linked Items dialog.
Frame
No
The Frame Number. An adder may contribute several frames to
an annunciator. The frame numbers are zero based.
LED
No
The number (zero based) of the first LED of a logical group. For
example, an HOA adder has three LEDs per slide switch. This
column would show 0 for Idx 0, 3 for Idx 1, etc. Due to the way
some adders are arranged (hardware) the LED numbers are in
irregular sequences.
Sw
No
The Switch number (if any) associated with the Idx.
Summary of Contents for Flex-Net Phase II
Page 1: ...Flex Net Phase II Application Guide LT 6045 Rev 1 October 2012 Application Guide...
Page 2: ......
Page 51: ...51 Hardware Layouts...
Page 115: ...114 Appendix B Using the Configurator...
Page 131: ......