115
Appendix B: Using the Configurator
•
Job Info
•
Shows details of the job's name, number, creation date and author. The multi-
line comments field can be edited and become part of the job's version history.
•
Options
•
Two Stage - check to enable two stage.
•
Fire Drill - check to enable the panel's Fire Drill switch.
•
Manual Signal Silence- check to enable the panel's Signal Silence switch.
•
Class A Conv Inputs - check this box to indicate that the panel has Class A
conventional inputs.
•
Class A Input Modules - check this box to indicate that input modules' field
wiring is Class A.
•
Class A Loop - check this box to indicate that the panel has Class A
addressable loop(s).
•
Class A Fire Phone - check this box to indicate that the wiring from an
addressable fire phone module and the handset is Class A.
•
Class A Network - check this box to indicate that the wiring between Network
Nodes is Class A.
•
Digital Audio - check this box to indicate that the audio signals use the Arcnet
wiring between Network Nodes. If not checked, then the audio runs over a
separate pair of wires.
•
Digital Phone - check this box to indicate that the Fire Phones use the Arcnet
wiring between Network Nodes. If not checked, then the phone conversations
use a separate pair of wires.
•
Monitor Alert
•
Second stage alarm relay - Sets alarm relay to operate on 2nd stage alarm.
Disabled unless Two Stage checked.
•
Relays follow node alarm - Sets Alarm relay to activate on node level alarm -
else system level alarm. Mutually exclusive with Second stage alarm relay.
•
Relays follow node supv - Sets Supervisory relay to activate on node level
supervisory - else system level supervisory.
•
Relays follow node trbl - Sets Trouble relay to activate on node level trouble -
else system level trouble.
•
Drift Compensation
•
Device LEDS flash when polled
•
Alarm transmit silence
•
Disable Auto Test - check this box to disable the automatic testing of System
Sensor addressable devices.
•
Automatic All Call - check this box to enable automatic "ALL-CALL" when PTT
or Digital message SW is pressed.
•
System Type - indicates the System Type (compact or large) of the current Job/
Version. This field cannot be editted, but for some products the job can be
converted between System Types. See Convert Job
•
Agency - choose between ULI Standard and ULC Standard.
•
Signal Coding
•
Coded System - check to enable coded system features.
•
Extended Code - Code pulse duration. 1/4 (disabled) 1/2(enabled).
•
Delay Code - Time between codes. 3 (disabled) 10 (enabled).
•
Signal Rates
•
Evac - choose the evacuation signal rate.
•
Alert - choose the alert signal rate.
Summary of Contents for Flex-Net Phase II
Page 1: ...Flex Net Phase II Application Guide LT 6045 Rev 1 October 2012 Application Guide...
Page 2: ......
Page 51: ...51 Hardware Layouts...
Page 115: ...114 Appendix B Using the Configurator...
Page 131: ......