103
(2) Specifications for RS-422/485 interface communication
With the set of Function F-42, select the specifications for RS-422/485 communication.
Function No.
Set value
Contents
F-42
00000
~ 13121
0
0
0
0
0
Data bit length
0: 7 bit, 1: 8 bit
Parity bit
0: No parity
1: Even parity
2: Odd parity
Stop bit
0: 1 bit, 1: 2 bit
Baud rate
0: 1 200 bps, 1: 2 400 bps
2: 4 800 bps, 3: 9 600 bps
Terminator
0: CR,1
:
CR
+
LF
[13020] is set as a default.
(3) Setting address for RS-422/485
With the set of Function F-43, setting address for RS-422/485 can be performed.
Setting range : [00] ~ [31]
[00] is set as a default.
(4) Change of data format of RS-232C and set digit of unit
With the set of Function F-49, set the change of data format and digit of unit.
Function No.
Set value
Contents
F-42
00000
~ 13121
0
0
Change of data
format
0 : Format 1, 1: Format 2
Set the digit of
unit.
0
:
2 digits, 1
:
3 digits
The data format 1 is the [7 digits load data with condition], and the data format 2 is [8 digits load
data without condition].
The digits for unit can be selectable from 2 digits or 3 digits at the time of Data format 1.
[Format 1] and [2 digits of unit] is selected as a default.