94
Scaling of analog output when the set value of CF-03 is 0 or 1
Maximum display
Display
+110 % of maximum display
Analog output
Approx.21.6 mA
Approx.11 V
Maximum value
20 mA
10 V
Minimum value 4 mA
0 V
0 Display
Approx.2.4 mA
Approx.
-
1 V
-10 % of maximum display
By CF-71, set the display when the minimum value is output.
By CF-72, set the display when the maximum value is output.
for example
CF-71: Set to 1 000
CF-72: Set to 5 000
Output the maximum value when the display is 5 000.
Output the minimum value when the display is 1 000.
5 000
Display
Analog output
Approx.21.6 mA
Approx.11 V
Maximum value
20 mA
10 V
Minimum value 4 mA
0 V
1 000
Approx.2.4 mA
Approx.
-
1 V
-10 % of maximum display
5 500
Set the value of CF-72 not to exceed the weighing capacity set in item 4.
Set the value of CF-72 smaller than the value of CF-71.