Measurements
35
5.2
Insulation resistance
The insulation resistance measurement is performed in order to ensure safety against electric
shock through insulation. Typical applications are:
insulation resistance between conductors of installation,
insulation resistance of non-conductive rooms (walls and floors),
insulation resistance of ground cables and
resistance of semi-conductive (antistatic) floors.
selection for instructions on
key functionality.
Figure 5.5: Insulation resistance
Test parameters for insulation resistance measurement
Uiso
Nominal test voltage
[50 V, 100 V, 250 V, 500 V, 1000 V, 2500 V*]
Limit
Minimum insulation resistance
[OFF, 0.01 M
÷ 200 M
]
* Nominal test voltage 2500 V is available on MI 3102H BT only.
Test circuits for insulation resistance
Figure 5.6: Connection of 3-wire test lead and tip commander (U
N
≤ 1 kV)