MI 3102(H) BT
Eurotest
XE
Measurements
40
R LOWΩ measurement procedure
Select continuity function using the function selector keys.
Set sub-function to
R LOWΩ
using
UP / DOWN
keys.
Enable and set
limit
(optional).
Connect
test cable to the instrument.
Compensate
the test leads resistance if necessary, (see section
Disconnect
from mains supply and discharge installation to be tested.
Connect
the test leads to the appropriate PE wiring (see
Press the
TEST
key to perform the measurement.
After the measurement is finished
store
the result by pressing the
MEM
button
(optional).
Figure 5.13: Example of RLOW result
Displayed result:
R
..............
R LOWΩ resistance
R+
............ result at positive polarity
R-
............. result at negative test polarity