MI 3102(H) BT
Eurotest
XE
Measurements
34
Voltage measurement procedure
Select the
VOLTAGE TRMS
function using the function selector keys.
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
).
Store
voltage measurement result by pressing the
MEM
key (optional).
Measurement runs immediately after selection of
VOLTAGE TRMS
function.
Figure 5.4: Examples of voltage measurement in three-phase system
Displayed results for single phase system:
Uln
........... voltage between phase and neutral conductors
Ulpe
......... voltage between phase and protective conductors
Unpe
........ voltage between neutral and protective conductors
f
................ frequency
Displayed results for three-phase system:
U12
........... voltage between phases L1 and L2
U13
........... voltage between phases L1 and L3
U23
........... voltage between phases L2 and L3
1.2.3
......... correct connection
– CW rotation sequence
3.2.1
......... invalid connection
– CCW rotation sequence
f
................ frequency
Displayed results for IT system (MI 3102 BT only):
U12
........... voltage between phases L1 and L2
U1pe
........ voltage between phase L1 and protective conductor
U2pe
........ voltage between phase L2 and protective conductor
f
................ frequency