MI 3102(H) BT
Eurotest
XE
Measurements
45
Loop resistance is indicative and calculated from Uc result (without additional proportional
factors) according to:
N
C
L
I
U
R
.
Figure 5.21: Example of contact voltage measurement results
Displayed results:
Uc
........ contact voltage
Rl
......... fault loop resistance
5.5.2 Trip-out time (RCDt)
Trip-out time measurement verifies the sensitivity of the RCD at different residual currents.
Trip-out time measurement procedure
Select the
RCD
function using the function selector keys.
Set sub-function to
RCDt
using
UP / DOWN
keys.
Set test
parameters
(if necessary).
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (optional).
Figure 5.22: Example of trip-out time measurement results
Displayed results:
t
............ trip-out time
Uc
........ contact voltage for rated I
N