MI 3102(H) BT
Eurotest
XE
Measurements
71
5.15
PE conductor resistance
In TN system instrument measures the resistance of the protection conductor from the power
transformer to the measurement site.
In TT system the resistance of protection conductor from mains outlet to earth electrode and
back to the power transformer via soil and the transformers earthling system is measured.
selection for instructions
on key functionality.
Figure 5.60: PE conductor resistance
Test parameters for PE conductor resistance measurement
Test
Selection of PE conductor resistance sub-function
[Rpe,Rpe(rcd)]
Lim
Maximum resistance
[OFF, 0.1
÷ 20.0
].
Circuits for measurement of PE conductor resistance
Figure 5.61: Connection of plug commander and 3-wire test lead
PE conductor resistance measurement procedure
Select the
Rpe
or
Rpe(rcd)
sub-function using the function selector keys and
UP /
DOWN
keys.
Select test
parameters
(optional).
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (optional).