MI 3102(H) BT
Eurotest
XE
Measurements
52
5.7.1 Line impedance and prospective short circuit current
Circuits for measurement of line impedance
Figure 5.31: Phase-neutral or phase-phase line impedance measurement
– connection of plug
commander and 3-wire test lead
Line impedance measurement procedure
Select the
Z LINE
function using the function selector keys.
Set sub-function to
Zline
using
UP / DOWN
keys.
Select test
parameters
(optional).
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (optional).
Figure 5.32: Examples of line impedance measurement result
Displayed results:
Z
............... line impedance
Isc
............ prospective short-circuit current
Lim
........... low limit prospective short-circuit current value
Prospective short circuit current is calculated as follows:
Z
k
Un
I
SC
SC
where:
Un ......... Nominal L-N or L1-L2 voltage (see table below),
ksc ........ Correction factor for Isc (see chapter
U
n
Input voltage range (L-N or L1-L2)
110 V (93 V
U
L-N
134 V)
230 V (185 V
U
L-N
266 V)
400 V (321 V
U
L-L
485 V)