![Juniper SRX550 Hardware Manual Download Page 91](http://html1.mh-extra.com/html/juniper/srx550/srx550_hardware-manual_2032212091.webp)
Figure 19: Connecting DC Power Cables
g034111
9. Replace the clear plastic cover over the terminal studs on the faceplate.
10. Verify that the power cables are connected correctly, that they are not touching or blocking access to
services gateway components, and that they do not drape where people could trip on them.
11. Remove the tape from the switch handle of the circuit breaker on the panel board that services the
DC circuit and switch the circuit breaker to the on position ( | ). Observe the status LEDs on the power
supply faceplate. If the power supply is correctly installed and functioning normally, the POWER LED
lights green steadily on the services gateway front panel.
NOTE:
If more than one power supply is being installed, turn on all power supplies at the same
time.
75
Summary of Contents for SRX550
Page 1: ...SRX550 Services Gateway Hardware Guide Published 2020 12 16...
Page 55: ...39...
Page 178: ...162...
Page 182: ...Restricted Access Warning 166...
Page 196: ...Jewelry Removal Warning 180...
Page 199: ...Operating Temperature Warning 183...
Page 206: ...190...
Page 210: ...194...
Page 213: ...197...