![Juniper SRX550 Hardware Manual Download Page 107](http://html1.mh-extra.com/html/juniper/srx550/srx550_hardware-manual_2032212107.webp)
NOTE:
The DC cable should be of minimum 14 AWG.
CAUTION:
You must ensure that power connections maintain the proper polarity.
The power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the
external DC power source at your site determines the color coding for the leads
on the power cables that attach to the terminals on the power supply.
5. Connect DC power cables to the A+ and A- terminals:
a. Remove the screws and square washers from the A+ and A- terminals. Use a Phillips (+) screwdriver,
number 2. The square washers are permanently attached to the screws.
b. Secure each power cable lug to the appropriate terminal with a screw. Apply between 23 lb-in.
(2.6 Nm) and 25 lb-in. (2.8 Nm) of torque to each screw.
•
Secure the positive (+) DC source power cable lug to the A+ (return) terminal.
•
Secure the negative (–) DC source power cable lug to the A- (input) terminal.
91
Summary of Contents for SRX550
Page 1: ...SRX550 Services Gateway Hardware Guide Published 2020 12 16...
Page 55: ...39...
Page 178: ...162...
Page 182: ...Restricted Access Warning 166...
Page 196: ...Jewelry Removal Warning 180...
Page 199: ...Operating Temperature Warning 183...
Page 206: ...190...
Page 210: ...194...
Page 213: ...197...