![Jung Smart Control SC 1000 KNX Product Documentation Download Page 80](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686080.webp)
Art. No. SC 1000 KNX
Figure 27: Button/rocker command depending on the configured function
i
With the rocker functions "dimming (brightness value)" and "Venetian blind/shutter
(position)" no slider is available on the start or favourite page for continuously changing the
value or position during a direct operation! Here, a value can be adjusted to the value
transmitter levels configured in the ETS by means of a long top-bottom operation of the
sensor surfaces.
i
With the functions "dimming (Start/Stop)" and "Venetian blind/shutter (Step/Move/Step)" a
distinction is made between a short and long press of a sensor surface. This is necessary
in order to distinguish between the commands for switching and dimming and for short and
long time operation. The actuation times can be configured in the ETS. With the functions
"dimming (brightness value)" and "Venetian blind/shutter (position)" the sensor surfaces
can be pressed long for value adjustment.
i
With the functions "1-byte value transmitter" and "2-byte value transmitter" it is possible to
switch off the operating function completely. In this case, the channel concerned only works
as a display function. Consequently, touching the display element does not induce any
response.
i
If the device's own timer is used, telegrams of the timer are transmitted to the bus for the
switching times via the objects of the KNX channels. The timer commands do not influence
the individually set button/rocker commands (transmission values) of the KNX channels,
however.
Example "value transmitter": The channel is set to the value "50" (button/rocker command)
in the ETS or by local operation on the device. The timer executes a switching command
with the value "75" and then transmits a telegram with this value via the channel object.
The actual transmission value of the channel ("50") is not affected by this. In the case of a
subsequent operation of the channel, the value "50" is transmitted to the bus.
Page 80 of 347
Software "Smart Control 501511"
Functional description