![Jung Smart Control SC 1000 KNX Product Documentation Download Page 248](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686248.webp)
Art. No. SC 1000 KNX
Automatic deactivation
of the display
illumination after
15s
30s
45s
1.0 min
1.5 min
2.0 min
5.0 min
10.0 min
15.0 min
30.0 min
1h
This parameter defines the time that
must elapse after an operation until the
display illumination is switched off
automatically. The parameter is only
effective when an automatic switch-off
has been provided by definition in the
parameters "Switch on display
illumination" and "Behaviour of switching
object display illumination".
h
Display -> Start page
Operation concept
Selection operation
Direct operation
Frequently used operating functions or
central functions can be stored on the
start page. The functions can be
operated either by selection operation or
direct operation. In the selection
operation, elements must first be
selected. Afterwards, operations are
performed by means of the control
command (switch on or off, move up or
down, ...). Alternatively, direct operation
is available for selection. In this case,
the control command is also executed
simultaneously time by touching the
operating element. This operation
concept is the same as the operation of
a push-button sensor. It can be used in
particular on the start page for
purposefully executing central functions
quickly and clearly (e.g. "All ON / All
OFF", "room lighting ON / OFF").
This parameter defines which operation
concept is used on the start page.
Grid start page
1-gang
2-gang
4-gang *
*: Only with selection
operation!
The start page has a defined display
grid. The grid defines the number of
KNX channels available on the start
page. 1, 2 or even 4 KNX channels can
be operational depending on the
operation concept. The size of the
operating elements varies depending on
the set grid.
Function 1 on the start
page
Not assigned
Channel 1 : Designation
...
Channel 30 : Designation
This parameter defines the assignment
of the first available function of the start
page to a KNX channel. 1, 2 or 4
functions are available depending on the
grid. It is important to note that the
channel assigned here is also actually
present in the configuration and has
been configured with the group
addresses! In the setting "Not assigned",
the function has no effect. The channels
24...30 are only available if no weather
station display page has been
configured.
Page 248 of 347
Software "Smart Control 501511"
Parameters