![Jung Smart Control SC 1000 KNX Product Documentation Download Page 231](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686231.webp)
Art. No. SC 1000 KNX
4.2.4.6.3 Setting switching times
There are basically two options when setting the switching times. The up to eight switching
times can be defined in the ETS plug-in as a presetting. Additionally, or alternatively, it is
possible to set or change each switching time directly on the device after commissioning.
Setting switching times in the ETS
The timer can be configured in the ETS in the parameter node of the same name. In this way, it
is possible to preset the switching times and thus adapt to the customer's later requirements
with regard to the channel assignments, switching times and channel commands. This requires
that the timer be configured centrally as "available" by the parameter of the same name in the
"Display" parameter node. Each of the up to 8 switching times will then have its own parameter
page with separate parameters. Each switching time has the same parameter set and thus has
the same scope of functions.
i
The switching times preset by the ETS and loaded into the device during commissioning
can be changed later at any time directly on the device on the display pages of the timer
(see page 232).
The following parameters are available per switching time...
-
Parameter "Switching time x (x = 1...8)":
This parameter specifies whether the switching time is active or inactive. Only active
switching times are executed. Inactive switching times in the ETS can subsequently be
activated on the device after commissioning. Similarly, activated switching times can
subsequently be deactivated on the display pages of the switching times by means of ETS.
-
Parameter "switching time hour" and "Switching time minute":
The actual switching time is specified here. The hours (0...23 / 24h format) and minutes
(0...59) of the switching time are subdivided into two parameter fields.
-
Parameter of the weekdays:
The parameters of the weekdays specify on which days of a calendar week the switching
time event is to take place. Each weekday has its own parameter. In the "active" setting,
the weekday of the switching time is assigned.
Active switching times have to be assigned to at least one weekday so that the channel
commands of these switching times are executed.
-
Parameter "Astro": This parameter defines whether the astro function is activated for the
switching time concerned (see page 229). The parameter additionally defines the astro
behaviour which determines whether a lighting (setting "light") or a blind, shutter or awning
(setting "shading") is activated by the astro function.
In the "no" setting, the astro function is inactive for the switching time.
-
Parameter "Random offset":
This parameter specifies whether the random function is activated for the switching
concerned (see page 230). If the setting is "yes", the assigned switching time is triggered
offset in a set random period (+/- 15 minutes). The "no" setting deactivates the random
function.