![Jung Smart Control SC 1000 KNX Product Documentation Download Page 53](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686053.webp)
Art. No. SC 1000 KNX
Function:
Channel function "Venetian blind (Step/Move/Step)
Object
h
137
Function
Dimming Feedb. Blind/shutter
height
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, W, -, (R)
2
Description
1-byte object for receiving position feedback telegrams for the blind/shutter
height, which a blind or rolling shutter actuator transmits, for example. The
status value, status icon and bar graph for the blind/shutter height visualisation
are influenced as a result. The feedback of the position value must be
transmitted by the "actively transmitting" actuator.
The decimal data values 0...255 are evaluated as percentages 0...100 % and
displayed in the device display.
Function:
Channel function "Venetian blind (Step/Move/Step)
Object
h
138
Function
Dimming Feedb. Slat pos.
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, W, -, (R)
2
Description
1-byte object for receiving position feedback telegrams for the slat position,
which a shutter actuator transmits, for example. The status value, status icon
and bar graph for the slat visualisation are influenced as a result. The
feedback of the position value must be transmitted by the "actively
transmitting" actuator.
The decimal data values 0...255 are evaluated as percentages 0...100 % and
displayed in the device display.
Function:
Channel function "Blind (position)"
Object
h
135
Function
Position of blind
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
3
Description
1 byte object to transmit value telegrams (0 ...255) for the blind/shutter height
setting. This can cause a blind position object (e.g. "Position Venetian blind",
"Position rolling shutter/awning", "Position venting louver"...) of a blind or
shutter actuator to be activated.
The transmitted decimal data values 0...255 must be evaluated by the actuator
as percentages 0...100 %.
Function:
Channel function "Blind (position)"
Object
h
136
Function
Venetian blind slat position
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
3
Description
1 byte object to transmit value telegrams (0 ...255) for the slat position setting.
This can cause a slat position object of a shutter actuator to be activated.
The transmitted decimal data values 0...255 must be evaluated by the actuator
as percentages 0...100 %.
1: The objects have been described for channel 1 as an example. The objects for the other
channels are defined in the same way by shifting the object number and changing the object
name.
2: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
3: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 53 of 347
Software "Smart Control 501511"
Object table