When changing over an operating mode, for example through local control, the KNX
switching object is updated by the controller and can be read out when the "Read" flag is
set. If the "Transmit" flag has been set for this object the current value will, in addition, be
automatically transmitted to the bus when it is changed.
After a device reset, the value corresponding to the set operating mode will be actively
transmitted to the bus if the "Transmit" flag has been set.
i
Change-over by the KNX object "Operating mode change-over" has the same priority as a
local change-over on the pushbutton sensor. An operating mode set by the object (e.g. by
a controller extension) can therefore be shifted by an operating mode change-over on the
device, if no higher-priority mode (e.g. window contact / motion detector) or the KNX forced
object is activated.
The KNX forced object will always have the highest priority.
i
In parameterisation of a presence button: the presence object will be active ("1") for the
period of an active comfort extension. The presence object will be automatically deleted
("0") if the comfort extension is stopped after the extension time has elapsed, or if the
operating mode has been changed by a higher-priority operation through the change-over
objects or by local control or a forced operating mode is deactivated by the KNX forced
object (forced object -> "00"). The controller therefore automatically resets the status of the
presence button when an object value is received via the operating mode objects or the
forced object is reset.
Page 186 of 347
Software "Smart Control 501511"
Functional description