![Jung Smart Control SC 1000 KNX Product Documentation Download Page 335](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686335.webp)
Art. No. SC 1000 KNX
Status indication (switching
object)
In the "Switching" and "Dimming" push-
button functions, the status LED signals
the status of the "Switching" object. The
object value is evaluated as follows:
"ON" -> "LED illuminated / OFF" -> LED
goes out.
Inverted status display
(switching object)
In the "Switching" and "Dimming" push-
button functions, the status LED signals
the inverted status of the "Switching"
object. The object value is evaluated as
follows: "ON" -> "LED illuminated / OFF"
-> LED goes out.
Status indication
The status LED indicates the status of
the push-button function "setpoint shift,
internal". The status is evaluated as
follows: "Shift active" -> LED illuminated
/ "Shift inactive" -> LED goes out.
Inverted status display.
The status LED indicates the inverted
status of the push-button function
"setpoint shift, internal". The status is
evaluated as follows: "Shift inactive" ->
LED illuminated / "Shift active" -> LED
goes out.
Control via separate LED
object
The status LED indicates the state of its
own, separate 1-bit LED object. This
setting causes the additional parameter
"Control of the status LED via object
value" to be shown.
Operating mode display
(KNX controller)
The status LED indicates the state of a
KNX room temperature controller via a
separate 1-byte communication object.
This setting causes the additional
parameter "Status LED ON with" to be
shown.
This setting cannot be configured with
the push-button functions "operating
mode switchover, internal", or "setpoint
shift, internal".
Comparator without sign
(1-byte)
The status LED is activated depending
on a comparison. In this configuration
there is a separate 1-byte
communication object available via
which the unsigned reference value
(0...255) is received. This setting causes
the additional parameter "Status LED
ON with" to be shown.
Comparator with sign
(1-byte)
The status LED is activated depending
on a comparison. In this configuration
there is a separate 1-byte
Page 335 of 347
Software "Smart Control 501511"
Parameters