In addition, the setpoint can be transmitted cyclically. The "Cyclical transmission of setpoint
temperature" parameter determines the cycle time (1 to 255 minutes). The value "0" will
deactivate the periodical transmission of the setpoint temperature value. It has to be pointed out
that with deactivated periodical transmission and deactivated automatic transmission, no
setpoint temperature telegrams will be transmitted in case of a change.
Setting the "Read" flag on the "Setpoint temperature" object makes it possible to read out the
current setpoint. Following the return of bus voltage or after re-programming via the ETS, the
object value will be initialised according to the current setpoint temperature value and actively
transmitted to the bus.