![Jung Smart Control SC 1000 KNX Product Documentation Download Page 210](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686210.webp)
Art. No. SC 1000 KNX
Bit of the status telegram
Meaning
0
On "1": Comfort operation activated
1
On "1": Standby mode active
2
On "1": Night mode active
3
On "1": Frost/heat protection mode active
4
On "1": Controller disabled
5
On "1": Heating, on "0": Cooling
6
On "1": Controller inactive (deadband)
7
On "1": Frost alarm (T
Room
≤ +5 °C)
Bit encoding of the 1 byte status telegram
Bit of the
status telegram
Meaning on "1"
Meaning on "0"
0
Normal operating mode
Forced operating mode
1
Comfort extension active
No comfort extension
2
Presence (Motion detector)
No presence
(Motion detector)
3
Presence (Presence button)
No presence
(Presence button)
4
Window opened
No window opened
5
Additional level active
Additional level inactive
6
Heat protection active
Heat protection inactive
7
Controller disabled
(dew point operation)
Controller not disabled
Bit encoding of the 1 byte additional status telegram
Page 210 of 347
Software "Smart Control 501511"
Functional description