Art. No. SC 1000 KNX
Object for command value output, cooling
Function:
Command value
Object
h
98
Function
Command value for cooling /
command value, basic
cooling
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the continuous command value of the cooling mode. In
two-level cooling mode, command value output for the basic cooling. This
object is only available in this way if the type of feedback control is configured
to "Continuous PI control".
Function:
Command value
Object
h
98
Function
Command value for cooling
(PWM) / command value,
basic cooling (PWM)
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description
1-bit object to output the PWM command value of the cooling mode. In two-
level cooling mode, command value output for the basic cooling. This object is
only available in this way if the type of feedback control is configured to
"Switching PI control (PWM)".
Function:
Command value
Object
h
98
Function
Command value for cooling /
command value, basic
cooling
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description
1-bit object to output the switching command value of the cooling mode. In
two-level cooling mode, command value output for the basic cooling. This
object is only available in this way if the type of feedback control is configured
to "Switching 2-point feedback control".
Object for command value output, additional cooling
Function:
Command value
Object
h
99
Function
Cmd. value, additional
cooling
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the continuous command value for additional cooling in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Continuous PI control".
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 41 of 347
Software "Smart Control 501511"
Object table