![Jung Smart Control SC 1000 KNX Product Documentation Download Page 324](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686324.webp)
Art. No. SC 1000 KNX
Temperature value of
the button for channel 1
(2)
Rocker 1.2 (0...40 °C)
0
...40
This parameter defines the temperature
value transmitted to the bus when the
bottom (or right-hand) rocker is pressed.
Visible only if "Function channel 1 (2) =
Temperature value transmitter (2
bytes)"!
Time between channel
1 and channel 2
Rocker 1.1
(1...255 x 100 ms)
0...
30
...255
Depending on the selected operation
concept, this parameter defines the
interval at which the push-button
transmits the telegram for channel 1 and
the telegram for channel 2 when the top
(or left side) of the rocker is pressed.
Time between channel
1 and channel 2
Rocker 1.2
(1...255 x 100 ms)
0...
30
...255
Depending on the selected operation
concept, this parameter defines the
interval at which the push-button
transmits the telegram for channel 1 and
the telegram for channel 2 when the
bottom (or right side) of the rocker is
pressed.
Full-surface operation
enabled
disabled
When the full-surface operation is
enabled, the ETS shows the following
parameters. Full-surface operation can
only be programmed if "Operation
concept = Channel 1 or channel 2"!
Function for full-surface
operation
Switching
Scene recall without
storage function
Scene recall with storage
function
In case of full-surface operation, this
parameter defines the function that is to
be used. The ETS shows the
corresponding communication object
and the other parameters.
If the push button sensor is to recall a
scene with storage function by full-
surface actuation, it will make a
distinction between a brief press (less
than 1 s), a sustained press (longer than
5 s) and an invalid button-press
(between 1 s and 5 s). A brief press
recalls the scene, a sustained press
stores a scene and an invalid full-
surface operation is ignored.
Visible only if "Full-surface operation =
enabled"!
Command for full-
surface operation
ON
OFF
TOGGLE
This parameter defines the value of the
transmitted telegram when a full-surface
operation has been sensed. "TOGGLE"
changes over the current object value.
Visible only if "Full-surface operation =
enabled"!
Scene number (1...64)
1
, 2, ... 64
Page 324 of 347
Software "Smart Control 501511"
Parameters