Art. No. SC 1000 KNX
Comfort mode remains active until the
motion detector ceases to detect
movement. In this setting, a presence
button on the device has no function.
Length of the comfort
extension
(0...255) * 1 min;
0 = OFF
0...
30
...255
When the presence button is pressed
from the Night mode or Frost/heat
protection, the controller switches to
Comfort mode for the length of time
specified here. When this time has
elapsed, it switches back automatically.
In the "0" setting, the comfort extension
is switched off, meaning that it cannot
be activated from Night or Frost/heat
protection mode. In this case, the
operating mode will not be changed,
although the presence function has
been activated.
This parameter is only visible when
presence detection is configured to
"Presence button".
Switch off controller
(dew point operation)
No
via bus
This parameter enables the "Disable
controller" object. If the controller is
disabled, there is no feedback control
until enabled in both control circuits
(command values = 0).
Valve protection
No
Yes
Valve protection may be carried out
periodically in order to prevent the
addressed control valves of the heater
or cooling system from becoming
calcified or stuck. The "Yes" setting in
this parameter activates valve
protection.
This type of protection is generally
started not only for non-active command
value outputs, i.e. for outputs which
have not requested any heating or
cooling energy over the past 24 hours.
For these outputs, the controller will
periodically set the command value to
the maximum value once a day for a
duration of approx. 5 minutes.
Switching time 1
not active
active
The device has an integrated weekly
timer and can be configured using the
ETS. The timer has up to 8 switching
times, which directly affect the
configured KNX channels (1...30) in the
device.
This parameter specifies whether the
first switching time is enabled or
disabled. Only active switching times are
executed. Inactive switching times in the
ETS can subsequently be activated on
the device after commissioning.
Similarly, activated switching times can
Page 304 of 347
Software "Smart Control 501511"
Parameters