Table 12. Service Request Numbers (continued)
Service
Request
Number
SRN
Src.
Failing
Function
Codes
Description and Action
805-649
G
software
Description: Problem log analysis indicates a machine check due to a
disabled I/O address space.
Action: Call the next level of support. For RS/6000 repairs, stand-alone
diagnostics are run by the service representative on all devices. Use any
SRN reported. If no other SRN is reported, suspect a software problem
805-802
G
152 210
Description: Over/Under voltage condition.
Action: Check AC line voltage per the Power MAP in your service guide. If
the AC line voltage is correct replace the listed FRUs.
805-805
G
152
Description: Cluster Bay shutdown due to loss of AC power.
Action: Refer to
″
MAP 1320: Visual Symptoms
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
805-812
D
152 210
Description: Over/Under voltage condition.
Action: Check the AC line voltage per the Power MAP in your service
guide. If the AC line voltage is correct replace the listed FRUs.
805-813
D
2E1 210
Description: Cluster Bay shutdown due to non-critical over temperature
condition.
Action:
1. Check for obstructions to cooling air flow.
2. Check for accumulated dust on the CPU and Planar.
If reasons 1 and 2 can be ruled out, then replace the listed FRUs.
806-619
G
221
Description: Problem log analysis indicates a machine check due to an
unidentified source on the I/O subsystem.
814-112
D
814
Description: The NVRAM test failed.
814-113
D
221
Description: The VPD test failed.
814-114
D
814
Description: I/O Card NVRAM test failed.
815-100
D
815
Description: The floating-point processor test failed.
815-101
D
815
Description: Floating point processor failed.
815-102
D
815
Description: Floating point processor failed.
815-200
D
815 7C1
Description: Floating point processor failed.
815–201
D
815
Description: The CPU card processor has a status of failed. CPU card
processors with a failed status are deconfigured and cannot be tested or
used by the system.
816-140
D
165 816
Description: The four-digit display test failed.
817-123
D
817
Description: The I/O Planar time-of-day clock test failed.
817-124
D
817
Description: Time of day RAM test failed.
817-210
D
817
Description: The time-of-day clock is at POR.
817-211
D
817 169
Description: Time of day POR test failed.
817-212
D
151 816
Description: The battery is low.
817-213
D
817
Description: The real-time clock is not running.
817-215
D
817
Description: Time of day clock not running test failed.
817-217
D
817 169
Description: Time of day clock not running.
Codes
Error Messages, Diagnostic Codes, and Service Reports, CHAPTER 9
125
Summary of Contents for E10
Page 2: ......
Page 68: ...52 VOLUME 3 ESS Service Guide...
Page 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Page 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Page 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Page 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Page 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Page 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Page 277: ......
Page 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...