Table 6. Firmware Error Codes. (continued)
Error
Code
Description
Action/ Possible Failing FRU
2BA00204 Service processor
firmware update error
occurred, update not
completed.
Error occurred while
calculate CRC write.
Refer to the actions in error code 2BA00200.
2BA00300 Service Processor
reports Slow Fan
number 1
The I/O planar connector for this fan is not detecting any simulated fan rotation
signals from the RPC cards.
Note: Go to
″
MAP 4740: Fan Check Detected by I/O Planar
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00301 Service Processor
reports Slow Fan
number 2.
See 2BA00300
2BA00302 Service Processor
reports Slow Fan
number 3.
See 2BA00300
2BA00303 Service Processor
reports Slow Fan
number 4.
See 2BA00300
2BA00309 Service Processor
reports Generic
Cooling Alert.
1. Check for air flow obstructions for the cluster bay.
2. Replace I/O Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00310 Service Processor
reports CPU Over
Temperature Alert.
1. Check for air flow obstructions for the cluster bay.
2. If the problem persists, replace CPU Card
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00311 Service Processor
reports I/O Over
Temperature Alert.
1. Check for air flow obstructions for the cluster bay.
2. Replace I/O Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00312 Service Processor
reports Memory Over
Temperature Alert.
1. Check for cool air flow obstructions to the system.
2. Replace Memory Card.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00313 Service Processor
reports Generic Power
Alert.
1. Use the service terminal to display and repair any related power problems.
Use the Show / Repair Problems Needing Repair option.
2. Replace I/O Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2BA00314 Service Processor
reports 5V Over
Voltage Alert.
1. Replace Electronics Cage Power Supply.
2. Replace I/O Planar.
One of the three electronics cage power supplies might be failing. Use the
service terminal to display problems needing repair and repair any related
problems. If none are found, replace the FRUs listed above until it is repaired.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
Codes
Error Messages, Diagnostic Codes, and Service Reports, CHAPTER 9
85
Summary of Contents for E10
Page 2: ......
Page 68: ...52 VOLUME 3 ESS Service Guide...
Page 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Page 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Page 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Page 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Page 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Page 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Page 277: ......
Page 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...