Table 6. Firmware Error Codes. (continued)
Error
Code
Description
Action/ Possible Failing FRU
4B2xxx51 LBIST fail
1. CPU card in slot P1-C1 (closest to the memory cards).
2. I/O planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B2xxx52 LBIST fail
1. CPU card in slot P1-C2 (farthest away from the memory cards).
2. I/O planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B200054 The CPU cards are
not compatible with
each other.
1. Remove cards
2. Verify part numbers
3. Install valid cards
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B200055 No CPU card in first
slot.
1. A CPU card must always be in slot P1-C1 (closest to the memory cards).
2. Replace the card in slot C1.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B200056 No CPU card in first
slot.
See error code 4B200055 action.
4B200057 The CPU cards are
not compatible with
each other.
Verify the CPU card part number.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B200058 Compatibility test on
CPU card in slot
P1-C1 (closest to
memory cards) failed.
Verify the CPU card part number.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B200059 Compatibility test on
CPU card in slot
P1-C2 (farthest away
from the memory
cards) failed.
Verify the CPU card part number.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B20000A No configured CPU
found.
For Model F10 and F20, see the Retain Tip for this error code or call the next
level of support. It may be possible to repair this error without replacing the CPU
card.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
Codes
96
VOLUME 3, ESS Service Guide
Summary of Contents for E10
Page 2: ......
Page 68: ...52 VOLUME 3 ESS Service Guide...
Page 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Page 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Page 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Page 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Page 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Page 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Page 277: ......
Page 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...