8
Precautions in Operation
1. Take noise prevention measures on the electronic devices installed in the same
equipment.
2. RC controllers shall be connected to the same 24-VDC power as a general rule. Our PS24
products can be connected in parallel, but if commercially available DC power supply units
are to be used, connect each controller’s power supply to common ground (0 V).
3. Make sure to have the emergency stop circuits for the XSEL controller and each RC
controller joint in the same system, so the input of emergency stop will be made at the
same time.
Error No. C65 “Servo on/off Logic Error” or Error No. E58 “Servo on/off Timeout Error” will
occur when only the RC controller side comes into the emergency stop condition while the
servo for a command from the XSEL controller is on.
Power
supply 1
+
-
Power
supply 2
+
-
0V (common)
Emergency stop ON!
ME0364-2B