Chapter 3 Operation
3.6 I/O Signal Controls and Function
131
(22) Operation for Direct Indication Mode
It is operated with the data set in the PLC's target position register, positioning width register,
setup speed register, acceleration/deceleration register and pressing current limit setup
register.
● Example of operation (Pressing operation)
(Preparation) Set the axis numbers to be used in Direct Indication Mode with Gateway
Parameter Setting Tool.
1) Set the target position data in the target position register.
2) Set the positioning width (pressing width) data in the positioning width register.
3) Set the speed data to the speed register.
4) Set the acceleration/deceleration data to the acceleration/deceleration register.
5) Set the pressing current limit data in the pressing current limit value register.
6) Turn “ON” the pressing setup (PUSH) signal.
7) Specify the pressing direction using the pressing direction setup (DIR) signal.
8) In the condition where the positioning completion (PEND) signal is turned “ON” or under
movement signal (MOVE) is turned “OFF”, turn “ON” the positioning start (CSTR) signal.
The data items set in Steps 1) through 5) are read in the controller at the startup (ON edge)
of the CSTR signal.
9) After the CSTR signal is turned “ON”, the PEND signal is turned OFF after tdpf.
10) After confirming that the PEND signal is turned “OFF” or MOVE signal is turned “ON”, turn
“OFF” the CSTR signal. Do not change any value in each register until the CSTR signal has
been turned “OFF”.
11) The current position data is continuously updated.
12) When the CSTR signal is turned “OFF” and the motor current reaches the current limit value
set in Step 5), the PEND signal is turned “ON”. (Pressing complete)
Even when the positioning width (pressing width) set in Step 2) is reached, in the case that
the current does not reach the motor current limit value set in Step 5), the pressing and a
miss (PSFL) signal is turned “ON”. In this case, the PEND signal is not turned “ON”.
(Pressing and a miss)
13) After the PEND signal or PSFL signal is turned “ON”, turn “OFF” the PUSH signal.
14) MOVE signal turns OFF at the same time as or within 10ms after PEND signal turns ON.
● Example of operation (Normal positioning operation)
For the general positioning operation, set the signal in Step 6) to “OFF”.
When the remaining travel distance becomes within the range of the positioning width set in the
position data, and the CSTR signal is turned “OFF”, the PEND signal is turned “ON”.
ME0302-4A
Summary of Contents for ERC3
Page 1: ...IAI Corporation ERC3 Gateway Unit Instruction Manual Forth Edition ...
Page 2: ......
Page 4: ...ME0302 4A ...
Page 8: ...ME0302 4A ...
Page 35: ...Chapter 1 Specifications Check 1 6 Option 27 1 6 Option はケーブル長 ME0302 4A ...
Page 54: ...Chapter 2 Wiring 2 3 Wiring Method 46 ME0302 4A ...
Page 158: ...Chapter 3 Operation 3 8 Field Network LED Indication 150 ME0302 4A ...
Page 160: ...Chapter 4 I O Parameter 152 ME0302 4A ...
Page 176: ...Chapter 5 Troubleshooting 5 4 Alarm List 168 ME0302 4A ...
Page 186: ......
Page 187: ......