7.3 Troubleshooting with no alarm generated
7-10
7.
Tro
ublesh
ooting
Abnormal or unstable operation
[Situation 1] Home return completes in the middle of home return operation
During home return operation, the ELECYLINDER moves until it hits the mechanical
end, then reverses and stops at home. When the load is excessive or the unit hits
interference, it may determine that the mechanical end has been reached, without
actually having done so.
No.
Possible cause
Confirmation/countermeasure
1
A load exceeding the maximum payload is
applied.
Reduce the load.
2
A moving part is hitting interference while
moving.
Remove the interfering object.
3
The body or guide is twisted due to the
fixing method of the ELECYLINDER.
● Loosen the fixing bolt and check whether the
moving part moves smoothly.
● If it does, check whether the mounting
surface is distorted.
● Re-mount according to the mounting method
described in the instruction manual.
→ For details, refer to "2.3 Installation
method".
4
The sliding resistance of the
ELECYLINDER is excessive.
Contact IAI.
Summary of Contents for ELECYLINDER EC-S13
Page 2: ......
Page 9: ...Chapter 12 Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ...
Page 10: ......
Page 66: ......
Page 116: ...3 38 3 Wiring ...
Page 136: ...4 18 4 Operation ...
Page 138: ......
Page 146: ......
Page 158: ...6 12 6 Parameters ...
Page 160: ......
Page 184: ...7 24 7 Troubleshooting ...
Page 186: ......
Page 230: ...8 6 How to replace components 8 44 8 Maintenance and Inspection Fan unit model number PSA FNB ...
Page 232: ......
Page 238: ...9 6 9 External Dimensions ...
Page 240: ......
Page 244: ...10 4 10 Life ...
Page 246: ......
Page 249: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ELECYLINDER Chapter12 ...
Page 250: ......
Page 256: ......
Page 257: ......