3.2 Electrical specifications
3-11
3. Wiring
Number of connectable regenerative resistor units (Option) (Reference)
Shown below is a reference of the number of regenerative resistor units (option) connectable.
For instance, if the total motor wattage of ELECYLINDER units is 800 W in horizontal orientation
and 400 W for the total in vertical orientation, take 800 W in Horizontal and 400 W in Vertical, find
the crossing point and you will see that the number of regenerative resistor unit you will need is
two units (reference).
Motor
wattage
Horizontal
0
200
400
600
800 1000 1200 1400 1600
Ver
tic
al
0
0
0
0
0
0
0
1
1
1
200
0
1
1
1
1
1
1
1
-
400
1
1
1
1
2
2
2
-
-
600
1
1
2
2
2
2
-
-
-
800
1
2
2
2
2
-
-
-
-
1000 2
2
2
2
-
-
-
-
-
1200 2
2
3
-
-
-
-
-
-
1400 2
3
-
-
-
-
-
-
-
1600 3
-
-
-
-
-
-
-
-
[Caution]
1. The values shown in the table above is a reference assuming that an actuator is ran back and
forth under the condition of rated acceleration/deceleration, rated load, 1000 mm stroke and
duty ratio at 50%.
2. Regenerative energy is absorbed also inside the controller. In case it exceeds the capacity,
the excess assumed regenerative electric discharge alarm should be generated. In such a
case, add a regenerative resistor unit externally.
In case the duty ratio of an operation is higher than 50% or the load in the vertical oriented
installation is large, it is necessary to have more regenerative resistor units than shown in the
table above.
The maximum number of regenerative resistor units connectable should be five units.
Do not attempt to connect more than five units as it could cause malfunction.
3. If you would require to find out the optimum number considering your operation condition, use
the calculation software to figure it out.
Summary of Contents for ELECYLINDER EC-S13
Page 2: ......
Page 9: ...Chapter 12 Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ...
Page 10: ......
Page 66: ......
Page 116: ...3 38 3 Wiring ...
Page 136: ...4 18 4 Operation ...
Page 138: ......
Page 146: ......
Page 158: ...6 12 6 Parameters ...
Page 160: ......
Page 184: ...7 24 7 Troubleshooting ...
Page 186: ......
Page 230: ...8 6 How to replace components 8 44 8 Maintenance and Inspection Fan unit model number PSA FNB ...
Page 232: ......
Page 238: ...9 6 9 External Dimensions ...
Page 240: ......
Page 244: ...10 4 10 Life ...
Page 246: ......
Page 249: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ELECYLINDER Chapter12 ...
Page 250: ......
Page 256: ......
Page 257: ......