7.3 Troubleshooting with no alarm generated
7-11
7.
Tro
ublesh
ooting
[Situation 2] The movement is complete, but the LS signal is not output
No.
Possible cause
Confirmation/countermeasure
1
LS signal (I/O signal) communication is not
established.
● Check the input/output status of the LS signal
(I/O signal) with the monitoring function of the
teaching tool.
(Both the master device and the
ELECYLINDER)
● Make sure the LS signal (I/O signal) voltage
is normal.
● Check whether the length of the I/O signal
cable is within 10 m, and whether the wire
diameter is thinner than the applicable value.
● Make sure the wiring processing is correct.
→ For details, refer to "3.4/3.5 Wiring
connections".