6.4 Parameter function descriptions
6-6
6. Parameter
s
6.4 Parameter function descriptions
Parameter No.1: Operation range adjustment
No. Category
Name
Symbol
Unit
Input range
Default setting
at shipping
1
A
Operation range
adjustment
LIMM
mm
0 to 9999.69 Maximum stroke
● The ELECYLINDER operation range can be adjusted to suit your system.
● The minimum setting unit is 0.01 mm.
● Set to your desired stroke length.
The controller automatically adds 0.30 mm and controls/monitors the operation range.
Set the operating stroke between 0 and 80 mm
by changing [Parameter No.1] to [80.00 mm].
Caution
Set within the ELECYLINDER movable range.
Setting to a value that exceeds the maximum stroke will result in collision with the
forward side mechanical stopper.
This may damage the ELECYLINDER, workpiece or peripheral devices.
Configuration example
0.30 mm
0.30 mm
80.00 mm
(Stroke to be used)
Parameter No.1:
80.00 mm
Summary of Contents for ELECYLINDER EC-S13
Page 2: ......
Page 9: ...Chapter 12 Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ...
Page 10: ......
Page 66: ......
Page 116: ...3 38 3 Wiring ...
Page 136: ...4 18 4 Operation ...
Page 138: ......
Page 146: ......
Page 158: ...6 12 6 Parameters ...
Page 160: ......
Page 184: ...7 24 7 Troubleshooting ...
Page 186: ......
Page 230: ...8 6 How to replace components 8 44 8 Maintenance and Inspection Fan unit model number PSA FNB ...
Page 232: ......
Page 238: ...9 6 9 External Dimensions ...
Page 240: ......
Page 244: ...10 4 10 Life ...
Page 246: ......
Page 249: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ELECYLINDER Chapter12 ...
Page 250: ......
Page 256: ......
Page 257: ......