7.4 Troubleshooting by alarm groups
7-23
7.
Tro
ublesh
ooting
Warnings in motor drive DC power supply PSA-200
The motor drive DC power supply PSA-200 has generated a warning.
No.
Warning name
Cause
Countermeasure
1
Internal relay life count
warning
Open/close count of the
internal relay has reached the
end of the life.
Replace the motor drive DC power
supply unit.
2
Electrolytic capacitor life
warning
The electrolytic capacitor has
reached the end of its life.
The warning being generated is
not stating there is no capacity in
the capacitor (dry-up), however, it
is recommended to have the motor
drive DC power supply replaced as
early as possible.
3
Fan revolution drop
warning
The fan revolution count has
dropped below the threshold.
The warning being generated is
not stating the fan revolution
count has stopped, however, it is
recommended to have the fan unit
replaced as early as possible.
Summary of Contents for ELECYLINDER EC-S13
Page 2: ......
Page 9: ...Chapter 12 Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ...
Page 10: ......
Page 66: ......
Page 116: ...3 38 3 Wiring ...
Page 136: ...4 18 4 Operation ...
Page 138: ......
Page 146: ......
Page 158: ...6 12 6 Parameters ...
Page 160: ......
Page 184: ...7 24 7 Troubleshooting ...
Page 186: ......
Page 230: ...8 6 How to replace components 8 44 8 Maintenance and Inspection Fan unit model number PSA FNB ...
Page 232: ......
Page 238: ...9 6 9 External Dimensions ...
Page 240: ......
Page 244: ...10 4 10 Life ...
Page 246: ......
Page 249: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 5 ELECYLINDER Chapter12 ...
Page 250: ......
Page 256: ......
Page 257: ......