Technical Data/Specifications
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
10-3
10.1.2 The HPS/RFL GARD Pro System Power Supply Specifications
Table 10-1 The HPS/RFL GARD Pro System Power Supply Specifications
Specifications
Power Supply Part Number
500305
500315
500325
Input Voltage
Range:
38-150Vdc or 96-132Vac
200-300Vdc or 200-240Vac
19-29Vdc
Max Output
Current:
+18V
-18V
4.00 Amps (combined total)
4.00 Amps (combined total)
4.00 Amps (combined total)
Adjustments:
none
none
none
Test Points:
TP1
TP2
TP3
+18 Volts nominal
Common
-18 Volts nominal
+18 Volts nominal
Common
-18 Volts nominal
+18 Volts nominal
Common
-18 Volts nominal
Indicators:
DS1
– Normal (Green)
DS1
– Normal (Green)
DS1
– Normal (Green)
Fuses: (2)
Manufactured Prior
to March 2016
4A, 250 V SLO-BLO
(3AG ¼ x 1¼)
2A, 250 V SLO-BLO
(3AG ¼ x 1¼)
10A, 32 V SLO-BLO
(3AG ¼ x 1¼)
Manufactured after
March 2016
4A, 250 V SLO-BLO
(5mm x 20mm)
2A, 250 V SLO-BLO
(5mm x 20mm)
10A, 32 V SLO-BLO
(5mm x 20mm)
Operating
Temperature:
-20
o
C to +70
o
C
-20
o
C to +70
o
C
-20
o
C to +70
o
C
Humidity:
95% @ +40
o
C
95% @ +40
o
C
95% @ +40
o
C
Isolation:
2500 Vdc isolation from
input terminals to ground,
and input terminals to
output terminals.
2500 Vdc isolation from input
terminals to ground, and
input terminals to output
terminals.
2500 Vdc isolation from
input terminals to ground,
and input terminals to
output terminals.
RFI Susceptibility:
ANSI PC37.90.2 (35 Volts/Meter)
IEC 255-22-3 (RFI Class III)
Interface Dielectric Strength:
All contact inputs, solid-state outputs, power supply inputs and relay outputs meet the following
specifications:
ANSI C37.90-1989 (Dielectric)
ANSI C37.90.1-1989 (SWC and Fast Transient))
EN 60255-5 (1500Vrms Breakdown Voltage and Impulse Withstand)